Eyewash and Emergency Shower Sign Requirements: OSHA 1910.151(c) and ANSI Z358.1

If someone can get a corrosive chemical in their eyes or on their body, they need water fast. OSHA requires the station. ANSI Z358.1 explains how to place and mark it.

OSHA 1910.151(c)

Where the eyes or body of any person may be exposed to injurious corrosive materials, suitable facilities for quick drenching or flushing of the eyes and body must be provided within the work area for immediate emergency use. Battery charging areas have their own flushing requirement under 1910.178(g).

ANSI Z358.1 in plain words

  • Close: reachable within about 10 seconds, which works out to roughly 55 feet of walking.
  • Same level as the hazard, with a clear path and no doors or obstacles in the way where possible.
  • Well lit and marked with a highly visible sign.
  • Tested weekly by activating it to flush the line and confirm it works.
  • Delivers tepid water and a 15-minute flush.

The sign matters because the person who needs the eyewash often cannot see well. Coworkers have to find it for them, fast.

Signs that meet this rule

All are checked. Uncheck any you already have, then add the rest in one click.

  • Eyewash Station
  • Emergency Shower
  • Battery Room Eyewash Station
  • First Aid Station
  • Corrosive Chemicals

Reference: 29 CFR 1910.151(c); 29 CFR 1910.178(g)(2); ANSI/ISEA Z358.1 (current edition).

This page is a plain-language summary to help you plan signs. It is not legal advice. Check the current standard and your local code or inspector for your exact situation.

Related: OSHA 1910.1200 HazCom · Forklifts and battery charging (1910.176, 1910.178) · All sign requirements