Fire Extinguisher Sign Requirements: OSHA 1910.157 and NFPA 10

Extinguishers only help if people can find them in a few seconds, through smoke, in a building they may not know.

OSHA 1910.157

  • Portable extinguishers must be mounted, located and identified so they are readily accessible without exposing employees to injury.
  • Travel distance to a Class A extinguisher may not exceed 75 feet. For Class B hazards it is 50 feet.
  • Extinguishers must get a visual inspection monthly and maintenance yearly.

NFPA 10

NFPA 10 says extinguishers must be conspicuously located and readily accessible, and kept clear of anything that blocks access or view. In large rooms, and anywhere visual obstructions cannot be avoided, a means to show the extinguisher location must be provided. A sign mounted high above the extinguisher, or a projecting sign seen down the aisle, is the usual answer.

Tips that pass inspections

  • Mount the sign high enough to be seen over racking, equipment and people.
  • Use a projecting or angled sign in long aisles so it reads from both directions.
  • Keep the floor area in front clear. A do not block sign stops pallets from landing there.

Signs that meet this rule

All are checked. Uncheck any you already have, then add the rest in one click.

  • Fire Extinguisher
  • Do Not Block Fire Extinguisher
  • Fire Suppression System
  • Fire Exit, Keep Clear

Reference: 29 CFR 1910.157(c), (d) and (e); NFPA 10, Standard for Portable Fire Extinguishers (current edition).

This page is a plain-language summary to help you plan signs. It is not legal advice. Check the current standard and your local code or inspector for your exact situation.